DELTACHILL
Chillers
34
Chillers
Technical Manual : 7022932_V1.9_11/2013
Cooling Performance EC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC011SR-04AK00
5
116.0
26.7
110.5
29.5
104.5
32.6
98.3
36.0
6
119.7
26.8
114.0
29.6
108.0
32.7
101.5
36.1
7
123.6
27.0
117.7
29.8
111.4
32.8
104.9
36.2
8
127.4
27.1
121.4
29.9
115.0
33.0
108.3
36.4
9
131.3
27.3
125.2
30.1
118.6
33.1
111.7
36.5
10
135.4
27.5
129.0
30.2
122.3
33.3
115.2
36.7
DCC014SR-04AL00
5
146.5
36.7
139.6
40.1
132.1
43.8
124.1
47.9
6
151.2
36.9
144.1
40.3
136.4
44.0
128.2
48.1
7
155.9
37.0
148.7
40.4
140.8
44.2
132.3
48.3
8
160.8
37.2
153.4
40.6
145.3
44.4
136.5
48.5
9
165.7
37.4
158.1
40.8
149.8
44.6
140.9
48.7
10
170.7
37.6
162.9
41.0
154.4
44.8
145.2
48.9
DCC017SR-04AM00
5
171.6
43.6
163.2
47.6
154.3
51.9
144.8
56.7
6
177.0
43.9
168.4
47.9
159.2
52.2
149.4
57.0
7
182.5
44.1
173.7
48.2
164.2
52.5
154.2
57.3
8
188.1
44.4
179.0
48.5
169.3
52.8
159.0
57.6
9
193.8
44.7
184.5
48.8
174.5
53.2
163.9
58.0
10
199.6
45.0
190.0
49.1
179.8
53.5
168.9
58.3
DCC021SR-04BS00
5
214.2
58.4
203.6
63.7
192.2
69.5
179.9
75.9
6
220.9
58.7
210.0
64.0
198.3
69.8
185.7
76.2
7
227.7
59.1
216.6
64.4
204.6
70.2
191.6
76.6
8
234.6
59.4
223.2
64.8
210.9
70.6
197.6
77.0
9
241.7
59.8
230.0
65.2
217.3
71.0
203.7
77.4
10
248.9
60.2
236.8
65.5
223.9
71.4
209.9
77.8
DCC023SR-04BT00
5
249.1
70.8
236.2
77.1
222.4
83.9
207.0
91.3
6
256.8
71.3
243.5
77.6
229.3
84.5
213.4
91.8
7
264.6
71.9
250.9
78.2
236.3
85.1
219.8
92.3
8
272.6
72.4
258.5
78.8
243.2
85.6
226.3
92.9
9
280.6
73.0
266.2
79.4
250.3
86.1
232.9
93.4
10
288.8
73.6
274.0
79.9
257.5
86.7
239.6
94.0
DCC024SR-06BT00
5
256.8
66.4
244.0
72.5
230.3
79.1
215.7
86.4
6
264.9
66.8
251.7
72.9
237.6
79.5
222.6
86.8
7
273.1
67.2
259.6
73.4
245.1
80.0
229.7
87.3
8
281.5
67.7
267.5
73.8
252.7
80.5
236.9
87.8
9
290.0
68.1
275.7
74.3
260.4
80.9
244.2
88.3
10
298.6
68.5
283.9
74.7
268.3
81.4
251.6
88.7
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x T)
6
For conditions outside of those quoted please refer to Airedale.