Chillers
Technical Manual : 7022932_V1.9_11/2013
Cooling Performance EC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC022DR-06AKK0
5
231.6
55.4
220.1
61.1
208.1
67.4
195.4
74.4
6
239.0
55.8
227.2
61.4
214.9
67.7
201.8
74.7
7
246.5
56.1
234.5
61.8
221.8
68.0
208.4
75.0
8
254.1
56.5
241.8
62.1
228.8
68.4
215.1
75.3
9
261.9
56.9
249.3
62.5
236.0
68.7
221.9
75.7
10
269.8
57.2
256.9
62.8
243.2
69.1
228.8
76.0
DCC024DR-04BKL0
5
253.3
70.5
240.0
77.0
225.6
84.1
210.3
91.9
6
261.2
71.0
247.4
77.5
232.6
84.6
216.9
92.4
7
269.1
71.5
254.9
77.9
239.7
85.0
223.6
92.9
8
277.0
72.0
262.5
78.4
247.0
85.6
230.4
93.4
9
285.1
72.5
270.2
78.9
254.3
86.1
237.3
93.9
10
293.4
73.0
278.1
79.5
261.7
86.6
244.3
94.5
DCC025DR-06BKL0
5
261.2
65.9
248.3
72.2
234.6
79.2
220.0
86.8
6
269.4
66.3
256.2
72.6
242.2
79.6
227.2
87.2
7
277.8
66.7
264.3
73.0
249.9
79.9
234.5
87.6
8
286.3
67.1
272.5
73.4
257.7
80.4
241.9
88.0
9
295.0
67.5
280.8
73.8
265.6
80.8
249.5
88.5
10
303.8
67.9
289.3
74.2
273.7
81.2
257.2
88.9
DCC027DR-04BLL0
5
278.9
81.7
263.9
88.8
247.5
96.4
229.9
104.9
6
287.5
82.3
271.9
89.3
255.0
97.0
236.9
105.4
7
296.0
82.8
280.0
89.9
262.6
97.6
244.0
106.0
8
304.6
83.4
288.1
90.4
270.4
98.1
251.3
106.6
9
313.4
83.9
296.4
91.0
278.2
98.7
258.6
107.2
10
322.2
84.5
304.8
91.5
286.1
99.3
266.0
107.8
DCC028DR-06BLL0
5
288.0
76.2
274.1
83.2
259.0
90.8
242.7
99.2
6
297.0
76.7
282.7
83.6
267.3
91.3
250.6
99.7
7
306.3
77.1
291.6
84.1
275.7
91.7
258.6
100.2
8
315.6
77.6
300.6
84.5
284.3
92.2
266.7
100.7
9
325.1
78.0
309.7
85.0
293.0
92.7
275.0
101.2
10
334.8
78.5
319.0
85.5
301.9
93.2
283.4
101.7
DCC030DR-06BLM0
5
313.2
83.7
297.8
91.2
281.2
99.5
263.3
108.6
6
323.0
84.2
307.1
91.8
290.1
100.1
271.7
109.2
7
333.0
84.8
316.7
92.4
299.1
100.7
280.3
109.8
8
343.1
85.4
326.3
93.0
308.3
101.3
289.0
110.4
9
353.4
85.9
336.2
93.6
317.7
101.9
297.9
111.1
10
363.8
86.5
346.2
94.2
327.2
102.5
306.9
111.7
DCC031DR-08BLM0
5
319.2
80.3
303.9
87.7
287.4
95.8
269.7
104.6
6
329.3
80.7
313.5
88.2
296.6
96.3
278.4
105.1
7
339.6
81.2
323.4
88.7
306.0
96.8
287.3
105.6
8
350.0
81.7
333.4
89.1
315.5
97.3
296.4
106.2
9
360.6
82.2
343.6
89.6
325.3
97.8
305.6
106.7
10
371.4
82.6
353.9
90.1
335.1
98.3
315.0
107.2
DCC032DR-06BMM0
5
335.0
91.0
318.3
99.1
300.5
108.1
281.4
117.9
6
345.4
91.6
328.2
99.8
309.8
108.8
290.2
118.6
7
355.9
92.3
338.3
100.5
319.4
109.5
299.3
119.3
8
366.7
93.0
348.5
101.2
329.1
110.2
308.5
120.0
9
377.6
93.7
358.9
101.9
339.0
110.9
317.8
120.8
10
388.6
94.4
369.5
102.7
349.1
111.7
327.3
121.5
DCC033DR-08BMM0
5
341.8
87.1
325.2
95.1
307.4
103.8
288.5
113.3
6
352.5
87.6
335.4
95.7
317.2
104.4
297.7
113.9
7
363.4
88.2
345.9
96.3
327.2
105.0
307.1
114.5
8
374.5
88.8
356.5
96.9
337.3
105.6
316.7
115.2
9
385.8
89.3
367.3
97.5
347.5
106.2
326.5
115.8
10
397.3
89.9
378.3
98.1
358.0
106.8
336.4
116.5
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x T)
6
For conditions outside of those quoted please refer to Airedale.