Chillers
DELTACHILL
Chillers
127
Technical Manual :7022932_V1.9_11/2013
Electrical Data Free Cool Chiller Extra Quiet Continued
ELECTRICAL DATA
DCF013DX-04ACD0
DCF014DX-04ADD0
DCF015DX-04ADF0
Unit Data
Nominal Run Amps
(1)
A
86.1
96.1
100.6
Maximum Start Amps
A
313.1
313.1
377.5
Recommended Mains Fuse Size
A
125
125
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0 / 43.1
43.1 / 43.1
43.1 / 47.5
Quantity
1 + 1
1 + 1
1 + 1
Motor Rating
kW
18.8 / 24.0
24.0 / 24.0
24.0 / 28.2
Sump Heater Rating
W
75
75
75
Start Amps
A
215 / 260
260 / 260
260 / 320
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
36.5
36.5
Circuit 2 Comp RLA (PFC)
36.5
36.5
42.8
Nominal Run Amps
A
75.0
83.0
89.3
Maximum Start Amps
A
306.5
306.5
372.8
Compressor Nominal Run Amps
A
28.5 / 36.5
36.5 / 36.5
36.5 / 42.8
Recommended Mains Fuse Size
A
125
125
125
Electronic Soft-start
Nominal Run Amps
A
86.1
96.1
100.6
Maximum Start Amps
A
199.0
209.1
245.1
Recommended Mains Fuse
A
125.0
125.0
125.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
75.0
83.0
89.3
Maximum Start Amps
A
194.5
202.5
238.5
Compressor Nominal Run Amps
A
28.5 / 36.5
36.5 / 36.5
36.5 / 42.8
Recommended Mains Fuse Size
A
125
125
125
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
N/A
N/A
N/A
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.6
6.6
6.6
Unit Nominal Run Amps
A
92.7
102.7
107.2
Recommended Mains Fuse Size
A
125
125
125
Motor Rating
kW
3
3
3
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
9.8
9.8
9.8
Unit Nominal Run Amps
A
95.9
105.9
110.4
Recommended Mains Fuse Size
A
125
125
125
Motor Rating
kW
4
4
4
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
92.4
102.4
106.9
Recommended Mains Fuse Size
A
125
125
125
Motor Rating
kW
3
3
3
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8
8
8
Unit Nominal Run Amps
A
94.1
104.1
108.6
Recommended Mains Fuse Size
A
125
125
125
Motor Rating
kW
4
4
4
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.