DELTACHILL
Chillers
66
Chillers
Technical Manual : 7022932_V1.9_11/2013
Electrical Data Regular Quiet Continued
ELECTRICAL DATA
DCC011DR-04ACC0
DCC013DR-04ACD0
DCC014DR-04ADD0
Unit Data
Nominal Run Amps
(1)
A
83.2
93.3
103.3
Maximum Start Amps
(2)
A
265.2
310.2
320.3
Recommended Mains Fuse Size
A
100
125
125
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
80
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
33.0 / 33.0
43.1 / 33.0
43.1 / 43.1
Quantity
1 + 1
1 + 1
1 + 1
Motor Rating
kW
18.8 / 18.8
24.0 / 18.8
24.0 / 24.0
Sump Heater Rating
W
75
75
75
Start Amps (2)
A
215 / 215
260 / 260
260 / 260
Type Of Start
Direct on line
Direct on line
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
28.5
36.5
36.5
Circuit 2 Comp RLA (PFC)
28.5
28.5
36.5
Nominal Run Amps
A
74.2
82.2
90.2
Maximum Start Amps
A
260.7
305.7
313.7
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 36.5
Recommended Mains Fuse Size
A
100
125
125
Electronic Soft-start
Nominal Run Amps
A
83.24
93.28
103.32
Maximum Start Amps
A
179.22
206.22
216.26
Recommended Mains Fuse
A
100
125
125
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
74.2
82.2
90.2
Maximum Start Amps
A
174.7
201.7
209.7
Compressor Nominal Run Amps
A
28.5 / 28.5
36.5 / 28.5
36.5 / 36.5
Recommended Mains Fuse Size
A
100
125
125
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
88.2
98.3
108.3
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
5
5
5
Unit Nominal Run Amps
A
88.2
98.3
108.3
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
4.5
4.5
4.5
Unit Nominal Run Amps
A
87.7
97.7
107.8
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
2.2
2.2
2.2
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
6.3
Unit Nominal Run Amps
A
89.5
99.6
109.6
Recommended Mains Fuse Size
A
100
125
125
Motor Rating
kW
3
3
3
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.