Chillers
DELTACHILL
Chillers
29
Technical Manual :7022932_V1.9_11/2013
Cooling Performance AC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC036DR-06BMS0
5
379.1
107.0
358.3
116.3
335.5
126.6
312.3
137.5
6
390.5
107.7
369.2
117.0
346.3
127.1
321.8
138.3
7
402.1
108.5
380.2
117.8
356.7
127.9
331.5
139.1
8
413.8
109.2
391.3
118.5
367.2
128.7
341.3
139.9
9
425.7
109.9
402.6
119.3
377.8
129.5
351.3
140.7
10
437.8
110.7
414.0
120.1
388.6
130.3
361.4
141.5
DCC038DR-10BMS0
5
400.2
103.4
381.1
112.3
360.3
121.9
337.4
132.3
6
412.9
103.9
393.3
112.8
371.8
122.3
348.3
132.8
7
425.9
104.4
405.7
113.3
383.5
122.8
359.4
133.2
8
439.0
104.8
418.4
113.8
395.4
123.3
370.6
133.8
9
452.4
105.3
431.1
114.3
407.5
123.8
382.0
134.3
10
466.1
105.8
444.0
114.7
419.8
124.3
393.6
134.8
DCC039DR-06BSS0
5
414.7
122.2
391.6
132.8
365.5
144.8
339.9
157.3
6
427.1
123.0
403.3
133.7
377.7
145.4
350.2
158.2
7
439.7
123.8
415.2
134.5
388.8
146.3
360.6
159.1
8
452.4
124.7
427.2
135.4
400.2
147.2
371.2
160.0
9
465.3
125.6
439.4
136.3
411.7
148.1
381.9
161.0
10
478.3
126.4
451.8
137.2
423.3
149.1
392.8
162.0
DCC042DR-10BSS0
5
441.6
116.5
419.9
126.4
396.3
137.2
370.7
149.1
6
455.4
117.0
433.1
126.9
408.9
137.7
382.6
149.6
7
469.4
117.5
446.6
127.4
421.7
138.2
394.7
150.2
8
483.7
118.0
460.2
127.9
434.7
138.8
407.0
150.7
9
498.3
118.5
474.1
128.4
447.9
139.3
419.5
151.3
10
513.0
119.0
488.3
129.0
461.3
139.9
432.2
151.9
DCC043DR-08BST0
5
466.4
129.6
441.2
140.7
414.1
152.9
385.1
166.3
6
480.2
130.3
454.4
141.5
426.7
153.8
397.0
167.2
7
494.3
131.1
467.8
142.4
439.4
154.6
409.0
168.1
8
508.6
132.0
481.4
143.2
452.3
155.5
421.1
169.0
9
523.1
132.8
495.3
144.1
465.4
156.4
433.4
169.9
10
537.9
133.6
509.3
145.0
478.7
157.3
445.9
170.9
DCC045DR-10BST0
5
477.6
127.3
453.2
138.2
426.9
150.0
398.6
163.0
6
492.4
128.0
467.3
138.8
440.3
150.7
411.2
163.8
7
507.5
128.6
481.7
139.5
453.9
151.4
424.0
164.5
8
522.8
129.3
496.3
140.2
467.7
152.2
437.0
165.2
9
538.3
130.0
511.1
140.9
481.7
152.9
450.2
166.0
10
554.1
130.7
526.1
141.7
496.0
153.6
463.7
166.8
DCC046DR-08BTT0
5
495.3
141.1
467.9
153.3
438.6
166.5
407.3
181.2
6
509.7
142.1
481.6
154.3
451.6
167.6
419.5
182.2
7
524.4
143.0
495.6
155.3
464.8
168.6
431.9
183.3
8
539.3
144.0
509.7
156.3
478.1
169.7
444.5
184.4
9
554.4
145.1
524.1
157.4
491.7
170.8
457.2
185.5
10
569.9
146.1
538.7
158.5
505.5
171.9
470.2
186.7
DCC048DR-10BTT0
5
508.3
138.0
481.7
149.8
453.2
162.7
422.6
176.8
6
523.9
138.8
496.5
150.6
467.2
163.6
435.8
177.7
7
539.7
139.6
511.6
151.5
481.4
164.4
449.1
178.6
8
555.8
140.4
526.9
152.4
495.9
165.3
462.7
179.6
9
572.2
141.3
542.4
153.3
510.6
166.3
476.5
180.5
10
588.7
142.1
558.2
154.2
525.5
167.2
490.5
181.5
DCC051DR-08BVV0
5
545.9
160.2
513.1
177.2
481.4
195.3
446.3
216.3
6
561.7
161.3
529.4
178.0
495.5
196.6
459.4
217.6
7
577.8
162.5
544.7
179.2
509.8
197.9
472.8
218.9
8
594.1
163.7
560.1
180.5
524.3
199.2
486.4
220.3
9
610.6
165.0
575.8
181.8
539.1
200.6
500.2
221.7
10
627.4
166.2
591.7
183.1
554.1
202.0
514.2
223.2
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x T)
6
For conditions outside of those quoted please refer to Airedale.