Cooling Performance AC Fans
Ambient (°C)
25
30
35
40
Model
Supply Temp
Output
Input
Output
Input
Output
Input
Output
Input
°C
kW
kW
kW
kW
kW
kW
kW
kW
DCC011DR-04ACC0
5
118.1
28.8
112.7
31.6
106.9
34.7
100.9
38.1
6
122.0
29.0
116.4
31.8
110.5
34.8
104.3
38.2
7
125.9
29.1
120.2
31.9
114.1
34.9
107.8
38.3
8
129.9
29.3
124.0
32.0
117.8
35.1
111.3
38.4
9
133.9
29.5
127.9
32.2
121.6
35.2
114.9
38.6
10
138.1
29.6
131.9
32.3
125.4
35.3
118.6
38.7
DCC013DR-04ACD0
5
134.9
33.7
128.8
36.8
122.0
40.1
114.7
43.7
6
139.3
33.9
133.0
36.9
126.0
40.2
118.5
43.8
7
143.7
34.1
137.2
37.1
130.1
40.3
122.4
43.9
8
148.3
34.2
141.6
37.2
134.2
40.5
126.4
44.1
9
152.9
34.4
146.0
37.4
138.5
40.6
130.4
44.2
10
157.6
34.6
150.5
37.5
142.8
40.8
134.5
44.4
DCC014DR-04ADD0
5
149.4
38.5
142.9
41.9
135.2
45.4
126.9
49.2
6
154.2
38.7
147.4
42.0
139.6
45.5
131.0
49.4
7
159.1
38.9
152.1
42.1
144.0
45.7
135.2
49.5
8
164.2
39.0
156.8
42.3
148.5
45.8
139.5
49.7
9
169.3
39.2
161.7
42.4
153.1
46.0
143.9
49.8
10
174.5
39.4
166.6
42.6
157.8
46.1
148.3
50.0
DCC015DR-04ADF0
5
162.7
41.9
155.1
45.5
146.5
49.3
137.2
53.5
6
167.9
42.1
160.0
45.7
151.2
49.5
141.7
53.7
7
173.2
42.3
165.0
45.9
155.9
49.7
146.2
53.9
8
178.6
42.5
170.1
46.1
160.8
49.9
150.8
54.1
9
184.1
42.7
175.3
46.3
165.7
50.1
155.4
54.3
10
189.6
42.9
180.5
46.5
170.7
50.3
160.1
54.6
DCC016DR-04AJJ0
5
169.3
43.6
160.6
47.4
151.5
51.6
141.9
56.3
6
174.7
43.8
165.9
47.6
156.5
51.8
146.6
56.5
7
180.2
44.0
171.2
47.8
161.6
52.0
151.4
56.6
8
185.9
44.1
176.6
48.0
166.8
52.2
156.3
56.8
9
191.6
44.3
182.1
48.2
172.0
52.4
161.3
57.0
10
197.5
44.5
187.7
48.4
177.3
52.6
166.3
57.3
DCC018DR-04BJK0
5
195.7
51.4
185.5
56.1
174.7
61.4
163.3
67.2
6
201.8
51.6
191.4
56.4
180.3
61.7
168.6
67.5
7
208.1
51.9
197.3
56.7
186.0
61.9
173.9
67.8
8
214.4
52.2
203.4
57.0
191.7
62.2
179.4
68.1
9
220.8
52.5
209.5
57.3
197.5
62.5
184.9
68.4
10
227.3
52.8
215.7
57.6
203.5
62.8
190.5
68.7
DCC019DR-04AFK0
5
202.2
52.4
191.6
57.1
180.3
62.4
168.4
68.1
6
208.5
52.7
197.6
57.4
186.0
62.7
173.7
68.5
7
214.8
53.0
203.7
57.8
191.8
63.0
179.2
68.8
8
221.3
53.3
209.9
58.1
197.7
63.3
184.7
69.1
9
227.9
53.6
216.2
58.4
203.6
63.7
190.3
69.5
10
234.6
54.0
222.5
58.8
209.7
64.0
196.0
69.8
DCC020DR-06AFK0
5
208.4
51.7
198.3
56.4
187.6
61.5
176.2
67.1
6
215.1
52.0
204.8
56.6
193.7
61.7
182.1
67.4
7
222.0
52.2
211.3
56.9
200.0
62.0
188.0
67.6
8
228.9
52.5
218.0
57.1
206.4
62.2
194.1
67.9
9
236.0
52.8
224.8
57.4
212.9
62.5
200.2
68.1
10
243.2
53.0
231.7
57.7
219.5
62.8
206.5
68.4
DCC021DR-04AKK0
5
226.1
59.4
214.0
65.1
201.2
71.4
187.7
78.4
6
233.1
59.7
220.7
65.4
207.5
71.7
193.6
78.8
7
240.2
60.1
227.4
65.8
213.9
72.1
199.7
79.1
8
247.4
60.5
234.3
66.2
220.4
72.5
205.8
79.5
9
254.7
60.9
241.2
66.6
227.0
72.9
212.0
79.9
10
262.1
61.4
248.3
67.0
233.7
73.3
218.3
80.4
1
Output kW refers to the chilled water duty.
2
Input kW refers to the unit input power (compressor + fans).
3
Duties applicable for chilled water T between 4 and 8°C.
4
Interpolate for water temperatures between those quoted, do not extrapolate.
5
Water flow rate (l/s) = Output ÷ (Cp x T)
6
For conditions outside of those quoted please refer to Airedale.