Design Features & Information
Specific Heat Capacity (SHC)
% Ethylene Glycol Concentration
Specific Heat Capacity (kJ/kgK)
% Propylene Glycol Concentration
Specific Heat Capacity (kJ/kgK)
Data quoted for water/glycol solutions at a nominal temperature of 10°C.
Only use the SHC data when calculating fluid VOLUME. Use figure for 0% concentration
(100% water) when applying Glycol Correction Factors, refer to Glycol Data, on page 24.
Minimum System Water Volume Calculations
METHOD 1
(Preferred Method)
Where the system permanent heat load is known, the minimum water volume in litres V
min
is:
Water Flow Rate (litres/minute) x Minimum Compressor Run
Time (mins) x Chiller Loading Factor
V
min
is the minimum water volume in litres
Minimum Compressor Run Time is 2 minutes
Minimum Turndown (kW) x 1.2
Chiller at 35°C Ambient, 7/12°C Water, Model DCC033DR-08BMM0 with a
permanent load of 129.6kW
Unit capacity at design conditions
Where the system permanent heat load is unknown:
Water Flow Rate (litres/hour) x Minimum Turndown Ratio x
1.2 Maximum number of compressor starts (per hour)
Chiller at 35°C Ambient, 7/12°C Water, Model DCC033DR-08BMM0
Unit capacity at design conditions