Chillers
Technical Manual : 7022932_V1.9_11/2013
Electrical Data Free Cool Chiller Extra Quiet Continued
ELECTRICAL DATA
DCF016DX-04AJJ0
DCF018DX-04BJK0
DCF020DX-06BFK0
Unit Data
Nominal Run Amps
(1)
A
118.0
130.0
128.5
Maximum Start Amps
A
271.0
312.0
401.0
Recommended Mains Fuse Size
A
160
160
160
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
100
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
6
Full Load Amps
A
2.5
2.5
2.5
Locked Rotor Amps
A
8.8
8.8
8.8
Motor Rating
kW
1.27
1.27
1.27
Condenser Fan - Per Fan (EC)
Quantity
4
4
6
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
27.0 / 27.0
27.0 / 33.0
47.5 / 33.0
Quantity
4
2 + 2
1 + 2
Motor Rating
kW
13.7 / 13.7
13.7 / 18.8
28.2 / 18.8
Sump Heater Rating
W
75
75
130 / 75
Start Amps
A
180 / 180
180 / 215
320 / 215
Type Of Start
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
20.9
20.9
42.8
Circuit 2 Comp RLA (PFC)
20.9
28.5
28.5
Nominal Run Amps
A
93.4
108.7
114.8
Maximum Start Amps
A
252.6
295.2
392.0
Compressor Nominal Run Amps
A
20.9 / 20.9
20.9 / 28.5
42.8 / 28.5
Recommended Mains Fuse Size
A
160
160
160
Electronic Soft-start
Nominal Run Amps
A
118.0
130.0
128.5
Maximum Start Amps
A
199.0
226.0
273.0
Recommended Mains Fuse
A
160.0
160.0
160.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
93.4
108.7
114.8
Maximum Start Amps
A
180.6
209.2
264.0
Compressor Nominal Run Amps
A
20.9 / 20.9
20.9 / 28.5
42.8 / 28.5
Recommended Mains Fuse Size
A
160
160
160
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
N/A
N/A
N/A
Full Load Amps
A
N/A
N/A
N/A
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
N/A
N/A
N/A
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
126.9
138.9
137.4
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
4
4
4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.8
11.8
11.8
Unit Nominal Run Amps
A
129.8
141.8
140.3
Recommended Mains Fuse Size
A
160
160
200
Motor Rating
kW
5.5
5.5
5.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
8
8
Unit Nominal Run Amps
A
124.3
138.0
136.5
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
3
4
4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8
11.2
11.2
Unit Nominal Run Amps
A
126.0
141.2
139.7
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
4
5.5
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.