Airedale DeltaChill FreeCool 110kW - 1080kW Manuel d'utilisateur Page 122

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 162
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 121
DELTACHILL
Chillers
122
Chillers
Technical Manual : 7022932_V1.9_11/2013
Electrical Data Free Cool Chiller Regular Quiet Continued
ELECTRICAL DATA
DCF015DR-04ADF0
DCF016DR-04AJJ0
DCF018DR-04BJK0
Unit Data
Nominal Run Amps
(1)
A
108.6
126.0
138.0
Maximum Start Amps
A
385.5
279.0
320.0
Recommended Mains Fuse Size
A
125
160
160
Mains Supply
VAC
400 V 3 PH 50 Hz
Max Mains Incoming Cable Size
mm²
Direct to Bus Bar
Recommended Permanent Fuse Size
A
16
16
16
Permanent Supply
VAC
230 V 1 PH 50 Hz
Max Permanent Incoming Cable Size
mm²
4 mm² terminals
Control Circuit
VAC
24V/230VAC
Evaporator
Pad Heater Rating
W
80
80
100
External Trace Heating
Available (fitted by others)
W
500
500
500
Condenser Fan - Per Fan (AC)
Quantity
4
4
4
Full Load Amps
A
4.3
4.3
4.3
Locked Rotor Amps
A
15
15
15
Motor Rating
kW
2
2
2
Condenser Fan - Per Fan (EC)
Quantity
4
4
4
Full Load Amps
A
3.9
3.9
3.9
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.56
2.56
2.56
Compressor - Per Compressor
Nominal Run Amps
A
43.1 / 47.5
27.0 / 27.0
27.0 / 33.0
Quantity
1 + 1
4
2 + 2
Motor Rating
kW
24.0 / 28.2
13.7 / 13.7
13.7 / 18.8
Sump Heater Rating
W
75
75
75
Start Amps
A
260 / 320
180 / 180
180 / 215
Type Of Start
Direct on line
Direct on line
Direct on line
OPTIONAL EXTRAS
Power Factor Correction
Circuit 1 Comp RLA (PFC)
36.5
20.9
20.9
Circuit 2 Comp RLA (PFC)
42.8
20.9
28.5
Nominal Run Amps
A
97.3
101.4
116.7
Maximum Start Amps
A
380.8
260.6
303.2
Compressor Nominal Run Amps
A
36.5 / 42.8
20.9 / 20.9
20.9 / 28.5
Recommended Mains Fuse Size
A
125
160
160
Electronic Soft-start
Nominal Run Amps
A
108.6
126.0
138.0
Maximum Start Amps
A
253.1
207.0
234.0
Recommended Mains Fuse
A
125.0
160.0
160.0
Power Factor Correction & Electronic Soft Start
Nominal Run Amps
A
97.3
101.4
116.7
Maximum Start Amps
A
246.5
188.6
217.2
Compressor Nominal Run Amps
A
36.5 / 42.8
20.9 / 20.9
20.9 / 28.5
Recommended Mains Fuse Size
A
125
160
160
Condenser Fan - Per Fan (EC Extra Freecooling)
Quantity
4
4
4
Full Load Amps
A
4.5
4.5
4.5
Locked Rotor Amps
A
N/A
N/A
N/A
Motor Rating
kW
2.86
2.86
2.86
Standard Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
8.9
8.9
8.9
Unit Nominal Run Amps
A
117.5
134.9
146.9
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
4
4
4
Larger Head Pump (Single or Run/Standby)
Pump Full Load Amps
A
11.8
11.8
11.8
Unit Nominal Run Amps
A
120.4
137.8
149.8
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
5.5
5.5
5.5
Standard Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
6.3
6.3
8
Unit Nominal Run Amps
A
114.9
132.3
146.0
Recommended Mains Fuse Size
A
125
160
160
Motor Rating
kW
3
3
4
Larger Head Inverter Pump (Single or Run/Standby)
Pump Full Load Amps
A
8
8
11.2
Unit Nominal Run Amps
A
116.6
134.0
149.2
Recommended Mains Fuse Size
A
160
160
160
Motor Rating
kW
4
4
5.5
(1) Based at 7.2°C Evap / 54.4°C Condensing, AC Standard Fans.
(2) Starting amps refers to the direct on line connections.
Vue de la page 121
1 2 ... 117 118 119 120 121 122 123 124 125 126 127 ... 161 162

Commentaires sur ces manuels

Pas de commentaire