Precision Air Conditioning
SmartCool
TM
D
Precision Air Conditioning
87
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical Data X2C0 Continued
SC25D067-X2C0-0 SC25D073-X2C0-0 SC25D080-X2C0-0
Standard Condenser Match 1 x CR105 1 x CR105 1 x CR105
Unit Data Full Function- X2C0
Nominal Run Amps A 88.6 90 93.8
Maximum Start Amps A 232.3 227.3 266.3
Recommended Mains Fuse Size A 100 100 125
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50Hz
Control circuit VAC 24 24 24
Unit Data Cooling Only X2C0
Nominal Run Amps A 62.80 65.68 73.38
Maximum Start Amps A 206.6 203 245.9
Recommended Mains Fuse Size A 80 80 100
Evaporator Fan Motor - Per Fan
Motor Type
AC AC AC
Quantity x Motor Size kW 3 x 2.38 3 x 2.38 3 x 2.38
Full Load Amps A 5 5 5
Locked Rotor Amps A 17.5 17.5 17.5
Compressor 1 , Circuit 1
Motor Size kW 10.86 12.15 13.73
Nominal Run Amps A 19.2 20.7 24.5
Locked Rotor Amps A 163 158 197
Type of Start Direct On Line
Compressor 2, Circuit 1
Motor Size kW 10.86 12.15 13.73
Nominal Run Amps A 19.2 20.7 24.5
Locked Rotor Amps A 163 158 197
Type of Start Direct On Line
Standard Condenser Match - AC Motor Per Fan
Quantity x Motor Size kW 3 x 0.6 3 x 0.6 3 x 0.6
Full Load Amps A 2.62 2.62 2.62
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat 3 3 3
Number of Elements 9 9 9
Rating (Total) kW 31.5 31.5 31.5
Current Per Phase A 45.47 45.47 45.47
Humidifier
Capacity kg/hr 15 15 15
Rating kW 11.25 11.25 11.25
Full Load Amps A 16.2 16.2 16.2
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size kW 3 x 2.2 3 x 2.2 3 x 2.2
Full Load Amps A 3.3 3.3 3.3
Locked Rotor Amps A 3.3 3.3 3.3
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size kW 3 x 3.1 3 x 3.1 3 x 3.1
Full Load Amps A 4.8 4.8 4.8
Locked Rotor Amps A 4.8 4.8 4.8
Standard Condenser Match - EC Motor-Per Fan
Quantity x Motor Size kW 3 x 0.73 3 x 0.73 3 x 0.73
Full Load Amps A 3.3 3.3 3.3
Condenser Match - SCAF Fan
Quantity x Motor Size kW 3 x 1.4 3 x 1.4 3 x 1.4
Full Load Amps A 6 6 6
(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
X2C0