SmartCool
TM
- D
Precision Air Conditioning
134
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Electrical DataW2F0 Continued
SC25D045-W2F0-0 SC25D050-W2F0-0 SC25D055-W2F0-0
Standard Dry Cooler Match 1 x DR55 1 x DR70 1 x DR70
Unit Data Full Function- W2F0
Nominal Run Amps (1) A 67.44 69.7 84.5
Maximum Start Amps A 154.2 148.8 174.4
Recommended Mains Fuse Size A 80 80 100
Max Mains Incoming Cable Size mm² 35 35 35
Mains Supply V 400V / 3PH + N / 50Hz
Control circuit VAC 24 24 24
Unit Data Cooling Only- W2F0
Nominal Run Amps A 50.4 52.7 56.8
Maximum Start Amps A 137.1 131.9 169.9
Recommended Mains Fuse Size A 63 63 80
Evaporator Fan Motor - Per Fan
Motor Type
AC AC EC
Quantity x Motor Size (2) kW 3 x 2.38 3 x 2.38 3 x 2.38
Full Load Amps A 5 5 5
Locked Rotor Amps A 17.5 17.5 17.5
Compressor 1 , Circuit 1
Motor Size (3) kW 6.3 7.2 7.2
Nominal Run Amps A 13.3 12.9 12.9
Locked Rotor Amps A 100 92 92
Type of Start Direct On Line
Compressor 2, Circuit 1
Motor Size (3) kW 6.3 7.2 9.5
Nominal Run Amps A 13.3 12.9 16.9
Locked Rotor Amps A 100 92 130
Type of Start Direct On Line
Standard Dry Cooler Match - Motor Per Fan
AC AC EC
Quantity x Motor Size kW 3 x 0.6 4 x 0.6 4 x 0.6
Full Load Amps A 2.62 2.62 2.62
OPTIONAL EXTRAS
Electric Heating
Number of stage of Reheat 2 2 3
Number of Elements 6 6 9
Rating (Total) kW 21 21 31.5
Current Per Phase A 30.3 30.3 45.47
Humidifier
Capacity kg/hr 8 8 8
Rating kW 6 6 6
Full Load Amps A 8.7 8.7 8.67
First upgrade Fan Motor - EC Motor - Per Fan
Quantity x Motor Size (2) kW 3 x 2.2 3 x 2.2 3 x 2.2
Full Load Amps A 3.3 3.3 3.3
Locked Rotor Amps A 3.3 3.3 3.3
Second upgrade Motor - EC Motor - Per Fan
Quantity x Motor Size (2) kW 3 x 3.1 3 x 3.1 3 x 3.1
Full Load Amps A 4.8 4.8 4.8
Locked Rotor Amps A 4.8 4.8 4.8
Standard Dry Cooler Match - EC Motor-Per Fan
Quantity x Motor Size (2) kW 3 x 0.73 4 x 0.73 4 x 0.73
Full Load Amps A 3.3 3.3 3.3
Dry Cooler Match - SCAF Fan
Quantity x Motor Size (2) kW 3 x 1.4 4 x 1.4 4 x 1.4
Full Load Amps A 6 6 6
(1) Values given for function units with standard selections for heating, humidification, supply air fans C evaporating and 54.4°C condensing.
(2) Stated motor power is based on maximum electrical power absorbed
(3) Values are per compressor
W2F0