Precision Air Conditioning
SmartCool
TM
– D
Precision Air Conditioning
151
Installation, Maintenance and Commissioning Manual :6877419 02/2013
INDOOR
UNIT
¡
ç
Mains Incoming Supply 400V / 3PH + N / 50Hz
¡
ç
¡
ç
¡
ç
¡
ç
INDOOR
UNIT
¡
è
Volt Free Alarm N/O
Non-Critical Alarm
¡
ç
Volt Free Alarm Common
¡
è
Volt Free Alarm N/O
Critical Alarm
¡
ç
Volt Free Alarm Common
¡
è
Volt Free Alarm N/C
¡
è
Fire Shutdown input
¡
ç
Healthy in N/C Condition
INDOOR
UNIT
502
¡
è
Remote On/OFF
522
¡
ç
INDOOR
UNIT
Rx-/Tx-
çè
Use Awg20/22 twisted pair (with overall shield)
cable, Belden ref. 8762 (Airedale ref:
6110316), or equivalent, for
network
çè ¡
Rx-/Tx-
INDOOR
UNIT
N + 1
Rx+/Tx+
çè çè ¡
Rx+/Tx+
GND
çè çè ¡
GND
In line with IEE Wiring Regulations, the following should be observed:
Extra low voltage control cables (ELV) and mains power cable should be segregated by a
minimum distance of 50mm
If cables must cross, it is recommended that they cross at right angles
Airedale recommends that ELV cables are screened at one end to earthed enclosures
C000