Installation, Maintenance and Commissioning Manual :6877419 02/2013
I
n
troduction
Designed to provide environmental precision air conditioning for applications such as
telecommunication facilities, data centers, computer rooms, clean rooms and
laboratories.
Description Capacity kW (1)
X2X2 Dual circuit direct expansion air cooled 55 -122
X2C0 Dual cool direct expansion air cooled and
chilled water
(X2) 30 82.5
(C0) 50 - 102
W2W2 Dual circuit direct expansion water cooled 54 -123
W2C0 Dual cool direct expansion water cooled and
chilled water
(W2) 30 - 85
(C0) 50 - 102
W2F0 Dual cool water cooled and glycol free cooling (W2) 30 - 86
(F0) 50 - 102
C000 Single circuit chilled water 69 -149
C0C0 Dual circuit chilled water 20 -102
(1) Based on nominal unit capacities
Full function units provide full control of temperature, humidity and filtration.
The modular design of the SmartCool allows grouping of differing model types and
capacities to be installed side by side. The flexibility of this type of installation provides for
multi-circuit functionality.
A full range of air cooled condensers is available with the direct expansion indoor units to
provide a matched system with optional performance upgrade, refer to Outdoor Unit
A full range of Dry coolers is available to complement the free cooling indoor units. Dry
coolers are a cost effective and safe solution against legionella.
Also available is a full range of Airedale water chillers to complement the chilled water
indoor units.
The range has been designed and optimised for operation with ozone benign refrigerant
R410A.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following
EC Directives:
Electromagnetic Compatibility Directive (EMC) 2004/108/EC
Low Voltage Directive (LVD) 2006/95/EC
Machinery Directive (MD) 89/392/EEC in the version
2006/427/EC
Pressure Equipment Directive (PED) 97/23/EC
To comply with these directives appropriate national & harmonised standards have been
applied. These are listed on the Declaration of Conformity, supplied with each product.