Precision Air Conditioning
SmartCool
TM
D
Precision Air Conditioning
201
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Positioning
· Unit must be positioned on an even base to ensure correct operation.
· Observe airflow and maintenance clearances.
· Where multiple units are installed, due care should be taken to avoid the
discharge air from each unit adversely affecting other units in the vicinity.
· When mounting the units adjacent to a wall or other vertical surface the
condenser should be positioned with the coil side facing the wall.
· Check all services are present and accessible.
Mounting
Fix the condenser down using the appropriate bolt holes in unit fixing legs.
Siting Recommendations
Horizontal Air Discharge
Avoid where possible siting the unit where wind and air re-circulation may interfere with
the fan operation.
A vertical air discharge unit is recommended for installation in windy locations or
wherever a horizontal air flow would be obstructed.
Pipework Connections
CAUTION
Take care that the service connections are correctly made and in particular do not
invert the inlet and outlet connections.
Pipework Connect
ions
sizes
CR12 CR16 CR22 CR30
Connections
Liquid Line - Sweat in 5/8 5/8 5/8 3/4
Discharge Line - Sweat in 5/8 5/8 5/8 3/4
CR50 CR65 CR80 CR105
Connections
Liquid Line - Sweat in 3/4 3/4 7/8 7/8
Discharge Line - Sweat in 1 1/8 1 1/8 1 3/8 1 3/8
CR CR CR CR
Connections
Liquid Line - Sweat in 3/4 3/4 7/8 7/8
Discharge Line - Sweat in 1 1/8 1 1/8 1 3/8 1 3/8
Holding Charge
The units are shipped with a holding charge of inert gas to guard against contamination or
moisture during shipping and storage.
CAUTION
The charge should be checked to indicate if leaks are present prior to evacuation.
If the charge appears to be either partially or totally lost, then the unit should be
carefully checked for signs of physical damage.
Pipework Installation
-
Good Practices
CAUTION
The following information is based on a complete matched Airedale system
using R410A.
General
Run the refrigeration lines taking care to ensure the following:
Use straight line routes where ever possible
Refrigerant lines should be insulated in areas of high/low temperature or when exposed
to direct sunlight
When insulating refrigerant lines, cut approximately 30 - 50cm longer than the distance
between the units to ensure the insulation goes right upto the unit, leave connections
uncovered for leak testing
Remove burrs to the ends of the copper tube, holding the tube downward to avoid
allowing dirt to contaminate the tube
Avoid any contact between the discharge line and the liquid line
OUTDOOR