Airedale SmartCool 11-233kW Manuel d'utilisateur Page 139

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 218
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 138
Precision Air Conditioning
SmartCool
TM
D
Precision Air Conditioning
139
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Waterside Pressure Drops W2F0
Water Cooled Condenser
0
100
200
300
400
500
600
700
0 1 2 3 4 5 6
Flow rate (l/s)
Pressure Drop (kPa)
1
2
3
Key
1 SC19D033 2
SC19D038 SC19D045,
SC25D045
3
SC19D064 SC19D76
SC25D050 SC31D083
(1) Includes plate condenser, 3 port valve and pipework.
(2) To calculate 3 port valve pressure drop:
DP valve =
2
÷
ø
ö
ç
è
æ
M
Q
where DP = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
÷
ø
ö
ç
è
æ
36
Kv
(3) Fluid 100% water
M
Values
Model Sizes SC19D33 SC19D38 D045 SC19D064-D076 SC25D45 SC25D50- D055 SC31D55-65 SC31D075-D083
Chilled Water Valve
0.51 1.11 1.75 1.11 1.75 1.75 1.75