Airedale SmartCool 11-233kW Manuel d'utilisateur Page 120

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 218
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 119
SmartCool
TM
- D
Precision Air Conditioning
120
Precision Air Conditioning
Installation, Maintenance and Commissioning Manual :6877419 02/2013
Waterside Pressure Drops W2C0
Water Cooled condenser (W2_ _)
0
100
200
300
400
500
600
700
0 1 2 3 4 5 6
Flow Rate (l/s)
Pressure Drop (kPa)
1
2
3
1 SC19D033 2 SC19D038 SC19D045,
SC25D045
3 SC19D064 SC19D076
SC25D050 SC31D083
(1) Includes plate condenser, 3 port valve and pipework.
(2) To calculate 3 port valve pressure drop:
DP valve =
2
÷
ø
ö
ç
è
æ
M
Q
where DP = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M =
÷
ø
ö
ç
è
æ
36
Kv
(3) Fluid 100% water, for glycol use.
M
V
alues
Model Sizes SC19D33-76
SC25D45-55
SC31D55-75
Water Valve (W2)
1.11
0.8
0.8
W2C0